Room Integrity and Gas Hold Time in Gaseous Fire Suppression Systems
A room integrity test is a technical test conducted to determine the leak tightness of a volume protected by a gaseous fire suppression system and its capacity to maintain the extinguishing gas for the required duration. It is also known in practice as a Door Fan Test or Enclosure Integrity Test. During the test, the leakage characteristics of the protected volume are measured, and the estimated gas hold time is calculated without discharging the actual extinguishing gas into the room.
In gaseous fire suppression systems, simply designing the correct amount of gas is not enough. Openings such as doors, cable transits, pipe penetrations, ventilation ducts, dampers, raised floors, and suspended ceilings also directly affect system performance. Therefore, checking room integrity is a crucial part of the system's commissioning and performance verification process.
The primary purpose of the test is to verify the room integrity, ensuring that when the gaseous fire suppression system is activated, the extinguishing gas remains in the protected volume for the required duration.
During a Door Fan Test, a special fan system is installed at the entrance door of the protected volume. The room is pressurized and depressurized in a controlled manner. Using the air flow and pressure values measured at different pressure levels, the leakage characteristics of the volume are determined.
| Stage | Application | Purpose |
|---|---|---|
| 1. Pre-check | Doors, seals, vents, cable transits, pipe penetrations, and the boundaries of the volume are checked. | To identify potential open points |
| 2. Equipment installation | The Door Fan system and pressure measurement equipment are mounted on the door. | To create a controlled test environment |
| 3. Pressure test | The volume is pressurized and depressurized at specific pressure levels. | To measure air leakage behavior |
| 4. Data analysis | Pressure and airflow measurements are evaluated. | To determine leakage characteristics |
| 5. Hold time calculation | The gas hold time is calculated using test data and volume properties. | To evaluate suppression performance |
| 6. Correction and retest | If necessary, leakage points are sealed and the test is repeated. | To meet acceptance criteria |
Hold Time is the minimum duration the discharged gas must remain within the protected volume after the activation of a gaseous suppression system to completely extinguish the fire and prevent potential re-ignition. Although this duration varies depending on the relevant standards and the gas used, it constitutes the fundamental success criterion of the room integrity test.