They are installed in each zone in Automatic Sprinkler Fire Suppression Systems to perform necessary tests and maintenance. They have the K factor of the sprinkler with the smallest orifice in the system. They have a sight glass on them to observe whether flow occurs. In addition to testing, there is a third position on them that provides complete drainage.

Threaded Test and Drain Valve

Product Details

Connection: Threaded

Approvals: UL Listed, FM Approved

Diameters: 1” – 2”

Maximum Working Pressure: 300 PSI


Product Material Details
Body Brass
Ball Brass
Gasket PTFE
Valve Diameter Orifice Diameter
1” ½”(K4.2), ½” (K5.6)
1 ¼” ½”(K4.2), ½” (K5.6)
1 ½”

½”(K4.2), ½” (K5.6)

¾”(K14), 1”(K25)
2”

½”(K4.2), ½” (K5.6)

¾”(K14), 1”(K25)

Test Drain Valve Diameter Determination – NFPA13

Pipe Diameter Test Drain Valve Diameter
2” and under ¾” and over
2 ½”, 3”, 3 ½” 1 ¼” and over
4” and over 2”


Grooved Test and Drain Valve

Product Details

Connection: Grooved

Approvals: UL Listed, FM Approved

Diameters: 1” – 2”

Maximum Working Pressure: 300 PSI


Product Material Details
Body Brass
Ball Brass
Gasket PTFE
Valve Diameter Orifice Diameter
1” ½”(K4.2), ½” (K5.6)
1 ¼” ½”(K4.2), ½” (K5.6)
1 ½”

½”(K4.2), ½” (K5.6)

¾”(K14), 1”(K25)
2”

½”(K4.2), ½” (K5.6)

¾”(K14), 1”(K25)

Test Drain Valve Diameter Determination – NFPA13

Pipe Diameter Test Drain Valve Diameter
2” and under ¾” and over
2 ½”, 3”, 3 ½” 1 ¼” and over
4” and over 2”