They are installed in each zone in Automatic Sprinkler Fire Suppression Systems to perform necessary tests and maintenance. They have the K factor of the sprinkler with the smallest orifice in the system. They have a sight glass on them to observe whether flow occurs. In addition to testing, there is a third position on them that provides complete drainage.
Connection: Threaded
Approvals: UL Listed, FM Approved
Diameters: 1” – 2”
Maximum Working Pressure: 300 PSI
| Body | Brass |
| Ball | Brass |
| Gasket | PTFE |
| Valve Diameter | Orifice Diameter |
| 1” | ½”(K4.2), ½” (K5.6) |
| 1 ¼” | ½”(K4.2), ½” (K5.6) |
| 1 ½” |
½”(K4.2), ½” (K5.6) |
| ¾”(K14), 1”(K25) | |
| 2” |
½”(K4.2), ½” (K5.6) |
| ¾”(K14), 1”(K25) |
Test Drain Valve Diameter Determination – NFPA13
| Pipe Diameter | Test Drain Valve Diameter |
| 2” and under | ¾” and over |
| 2 ½”, 3”, 3 ½” | 1 ¼” and over |
| 4” and over | 2” |
Connection: Grooved
Approvals: UL Listed, FM Approved
Diameters: 1” – 2”
Maximum Working Pressure: 300 PSI
| Body | Brass |
| Ball | Brass |
| Gasket | PTFE |
| Valve Diameter | Orifice Diameter |
| 1” | ½”(K4.2), ½” (K5.6) |
| 1 ¼” | ½”(K4.2), ½” (K5.6) |
| 1 ½” |
½”(K4.2), ½” (K5.6) |
| ¾”(K14), 1”(K25) | |
| 2” |
½”(K4.2), ½” (K5.6) |
| ¾”(K14), 1”(K25) |
Test Drain Valve Diameter Determination – NFPA13
| Pipe Diameter | Test Drain Valve Diameter |
| 2” and under | ¾” and over |
| 2 ½”, 3”, 3 ½” | 1 ¼” and over |
| 4” and over | 2” |