Internationally Approved Product
TORNATECH

A diesel fire pump controller automatically starts the diesel engine-driven fire pump when system pressure drops. The controller also monitors the engine and batteries and reports faults as alarms. Engine voltage, battery banks and alarm connections are evaluated together when selecting a diesel pump controller.
The Tornatech Model GPD is a controller built to the latest edition of NFPA 20, listed under UL 218 and FM Global Class 1321/1323 approved. Its 7″ colour touchscreen ViZiTouch V2.1 operator interface presents pressure, battery voltage, charging current and alarm information on a single screen.
The controller has two independent, fully automatic battery chargers. The engine is cranked with alternating 15-second attempts from battery 1 and battery 2. Date-stamped pressure and event logs can be viewed on the screen and downloaded via USB or a smartphone app.
Weekly test timer, minimum run time and sequential start timers can be adjusted in the field. Modbus TCP/IP communication and remote alarm contacts allow integration with building automation systems.
| Specification | Value |
|---|---|
| Standards and Approvals | NFPA 20; UL 218 (EX3971); FM Class 1321/1323; New York City acceptance |
| DC System | 12 VDC or 24 VDC |
| AC Supply | 120 V/1 ph/60 Hz or 208–240 V/1 ph/50–60 Hz |
| Battery Chargers | 2, independent; 10 A continuous, 500 mA trickle charge; max. 220 Ah battery |
| Cranking Cycle | 6 attempts; alternating 15 s crank from battery 1/2, 15 s rest |
| Pressure Sensing | External transducer 0–500 psi, 1/2″ female NPT |
| Enclosure Rating | NEMA 2 (Canada/UAE manufacture); IP55 (European manufacture) |
| Ambient Temperature | 4 – 40 °C standard; 55 °C optional |
Technical values are based on manufacturer documents; confirm against the current data sheet before ordering.
Diesel engine fire pump stations
Sprinkler, fire hose cabinet and hydrant systems
Packaged and container-type fire pump rooms
Facilities where mains power is unreliableOther equipment considered together with the Diesel Fire Pump Controller in the fire pump room: