Waste Cone with Sight Glass

Waste Cone with Sight Glass

Waste Cone with Sight Glass – relief valve outlet

A waste cone with sight glass is installed at the outlet of the fire pump relief valve and allows the flow of water relieved through the valve to be checked visually. The relief valve outlet connection and the need for visual flow verification are considered when selecting a fire pump waste cone.

 

Cla-Val WC-1 Fire Pump Waste Cone

The Cla-Val Model WC-1 is designed for use with UL/FM approved fire pump pressure relief valves and is manufactured in accordance with NFPA 20 requirements. Two 2″ 316 stainless steel sight glasses on the conical body make it easy to check whether the relief valve is open.

The body is cast in one piece from ASTM A536-65 ductile iron and contains no welds. Interior and exterior surfaces are coated with fusion-bonded red epoxy. It is supplied as standard with 150# FF and 300# RF flanges.

Suitable for onshore and offshore applications, the WC-1 can also be manufactured in optional materials such as NAB, Monel, 316 stainless and super duplex for seawater and heavy-duty conditions. Size is selected according to pump flow. Waste cones can also be supplied under the Weflo brand.

Waste Cone with Sight Glass Technical Specifications

SpecificationValue
Sizes (Inlet × Outlet)3″×5″, 3″×6″, 4″×6″, 4″×8″, 6″×8″, 6″×10″, 8″×12″, 8″×14″
Pump Flow0 – 5,000 GPM (depending on size)
FrameDuctile iron ASTM A536-65, one-piece casting (no welds)
Sight Glass2 × 2″ 316 stainless steel
CoatingFusion-bonded red epoxy (interior and exterior)
Flanges150# FF / 300# RF (standard)
DesignManufactured to NFPA 20; for UL/FM approved pump relief valves

Technical values are based on manufacturer documents; confirm against the current data sheet before ordering.

Waste Cone with Sight Glass Applications

Monitoring flow at the fire pump relief valve outletMonitoring flow at the fire pump relief valve outlet
Onshore and offshore fire pump stationsOnshore and offshore fire pump stations
Fire pump systems operating on seawaterFire pump systems operating on seawater

Related Fire Pump Accessories

Other equipment considered together with the Waste Cone with Sight Glass in the fire pump room:

Frequently Asked Questions

What does a waste cone do?
It allows the flow of water relieved from the relief valve to be checked visually through the sight glasses.
Where is the waste cone installed?
It is installed at the outlet of the fire pump main relief valve. The manufacturer recommends the WC-1 for the outlet of its own relief valves.
Which size should be selected?
Size is selected according to pump flow. For example, 3″×5″ is used for 0–450 GPM, 6″×8″ for 1,000–1,500 GPM and 8″×14″ for 3,500–5,000 GPM.
Are there welds in the body?
No. The WC-1 has a one-piece cast body.
Can it be used in seawater applications?
Yes. The WC-1 is also specified for offshore applications and can be manufactured in optional materials suitable for seawater.
Which flange types are available?
Flat-face (FF) flanges in Class 150# and raised-face (RF) flanges in Class 300# are offered as standard.