Jockey Pump Controller

Jockey Pump Controller

Jockey Pump Controller – pressure control

A jockey pump controller controls the jockey (pressure maintenance) pump used to maintain pressure in fire pump systems. According to Tornatech, the jockey pump prevents the main fire pump from starting unnecessarily because of small leaks in the sprinkler installation. Motor power, system pressure and cut-in settings are evaluated together when selecting a jockey pump controller.

 

Tornatech JPLT-B Jockey Pump Controller

The Tornatech JPLT-B is supplied with a ViZiLT operator interface mounted on the front door. Start and stop pressures, timers and the unit of measure (psi or bar) can be set without opening the door. The display shows system pressure, set points, operating status, motor overload information, number of starts and a non-resettable run-hour counter.

The power circuit consists of a horsepower-rated disconnect switch, a thermal-magnetic motor protector and a motor contactor for across-the-line starting. The fuseless motor starter is operated by a rotary handle that can be padlocked and is interlocked with the door.

The controller senses pressure with a 316 stainless steel pressure transducer operating in the 0–600 psi range and is offered for jockey pump motors from 0.25 to 25 HP. The JPLT is listed under UL 508A.

Jockey Pump Controller Technical Specifications

SpecificationValue
StartingAcross-the-line (full voltage)
Power Range0.25 – 25 HP (depending on supply voltage)
Supply110–120 V and 200–240 V/1 ph; 200–600 V/3 ph
Operator InterfaceViZiLT, alphanumeric display, H-O-A and menu buttons
Pressure Transducer0–600 psi, 316 stainless steel, 1/2″ brass male NPT
Control Circuit24 V AC
Enclosure RatingNEMA 2 standard (European manufacture: IP55)
ListingUL 508A; New York City acceptance; CE optional

Technical values are based on manufacturer documents; confirm against the current data sheet before ordering.

Jockey Pump Controller Applications

Pressure maintenance in fire pump stationsPressure maintenance in fire pump stations
Compensating for small leaks in sprinkler installationsCompensating for small leaks in sprinkler installations
Pump rooms together with electric and diesel fire pump controllersPump rooms together with electric and diesel fire pump controllers

Related Fire Pump Accessories

Other equipment considered together with the Jockey Pump Controller in the fire pump room:

Frequently Asked Questions

Why is a jockey pump used?
It maintains system pressure and prevents the main fire pump from starting unnecessarily because of small leaks in the installation.
Which power range is the JPLT-B used for?
From 0.25 HP to 25 HP. Maximum power depends on supply voltage; for example 15 HP at 380–415 V 3-phase and 25 HP at 575–600 V 3-phase.
Is it necessary to open the controller door to change settings?
No. Thanks to the ViZiLT interface, pressure settings, timers and unit of measure can be adjusted without opening the door.
Which pressure transducer does the controller use?
It uses a transducer with a 0–600 psi range, 316 stainless steel body and 1/2″ brass male NPT connection.
Is the JPLT-B UL 218 listed?
No. The JPLT is listed under UL 508A (industrial control panels). The UL 218 listing applies to main fire pump controllers.
Which counters does the controller have?
It has a pump start counter and a non-resettable run-hour counter.