Internationally Approved Product
TORNATECH

An electric motor fire pump controller is a full-service control unit that automatically starts the electric motor driving the fire pump when system pressure drops. Motor power, supply voltage and starting method are evaluated together when selecting an electric fire pump controller.
The Tornatech GPx series consists of models with different starting methods. The GPA is across-the-line, the GPY and GPW are wye-delta, the GPP is part winding, the GPR is autotransformer and the GPS is soft start/soft stop. This allows a model to be chosen to suit the motor power and the starting current capacity of the supply.
A 7″ ViZiTouch 2.1 touchscreen, simultaneous display of three-phase voltage and current, and a pressure and event recorder are standard on all models. The isolating switch and circuit breaker are operated by a single handle and mechanically interlocked with the door. A surge arrester, locked rotor protection, phase sequence indication and emergency start handle are also standard.
The controllers can be supplied with a GPU automatic transfer switch so that the pump can be powered from an alternate source during a mains failure. The GPx series is listed under UL 218 and FM Class 1321/1323 approved.
| Specification | Value |
|---|---|
| Models | GPA, GPY, GPW, GPP, GPR, GPS (+ GPU transfer switch) |
| Standards and Approvals | NFPA 20; UL 218 and UL 1008; FM Class 1321/1323; New York City acceptance |
| Operator Interface | ViZiTouch 2.1, 7″ colour touchscreen |
| Short-Circuit Withstand Rating (GPA) | 200 – 480 V: 100 kA; 600 V: 50 kA |
| Locked Rotor Protection | Trips within 8 – 20 s at 600% of motor full-load current |
| Enclosure Rating | NEMA 2 (Canada/UAE manufacture); IP55 (European manufacture) |
| Ambient Conditions | 4 – 40 °C, 5 – 80% relative humidity; 55 °C optional |
Technical values are based on manufacturer documents; confirm against the current data sheet before ordering.
Electric motor fire pump stations
Facilities supplied by mains and generator (with GPU)
Sprinkler, fire hose cabinet and hydrant systems
Pump rooms with high ambient temperature (55 °C option)Other equipment considered together with the Electric Motor Fire Pump Controller in the fire pump room: